It's not really a mystery.links 'n stuffMy video on 240V power in the US;https://youtu.be/jMmUoZh3Hq4This channel is supported through viewer contributions o...
2 kW @ 120 V is 16.7 A, which exceeds the 15 A limit on most household wiring in North America. To be able to achieve that you’d need to get a 20 A rated circuit installed by an electrician which means pulling out and replacing the wiring with a heavier gauge.
The advantage of 240 V rating in the UK is that you can draw more power with less current, so you don’t need the wiring to be so heavy for a high power appliance like a kettle.
2 kW @ 120 V is 16.7 A, which exceeds the 15 A limit on most household wiring in North America. To be able to achieve that you’d need to get a 20 A rated circuit installed by an electrician which means pulling out and replacing the wiring with a heavier gauge.
The advantage of 240 V rating in the UK is that you can draw more power with less current, so you don’t need the wiring to be so heavy for a high power appliance like a kettle.
yes. a 1.5 kw heater at 120 and a 1.5 kw heater on 240v would draw different amps but they would heat water at the same rate.